Authorized distributor of exide industrial batteries
Corporate Client Sitemap
TUBULAR BATTERIES



Exide EL Range of Tubular Monobloc Batteries


CAPACITIES WEIGHTS & DIMENSIONS
 
Capacity in Ah at 27° C When discharged for
Charge Current (A)
 
Approx. Battery Weight
Approx. acid Qty (1.220 Sp.Gr./cell)
Overall Dimensions
Trickel Charge
Current mA
Type
10 Hr.
10 Hr.
Nominal Monobloc
Unit Voltage
Starting
Finishing
Minimum Ah Input during  Intial Charge
Without Acid  (KG)
± 5%
Filled with Acid (KG)
± 5%
Litres
L
mm
± 3
W
mm
±3
H
mm
±3
Min
Max
Final Voltage
per cell (V)
1.75
1.8
(Conforms to BIS 13369)
_______
2.35
2.70
                 
6EL 40
40
38
12
4.8
2.4
180
13.5
19.2
0.8
260
173
240
40
160
6EL 50
50
47
12
6
3
225
19
25
0.85
410
176
249
50
200
6EL 66
66
63
12
7.92
3.96
297
23
31.7
1.2
410
176
249
66
264
6EL 75
75
71
12
9
4.5
337
25
33.5
1.18
410
176
249
75
300
6EL 100
100
95
12
12
6
450
34.5
47.5
1.85
506
220
257
100
400



Exide EL TALL Tubular Range


CAPACITIES WEIGHTS & DIMENSIONS
 
Capacity in Ah at 27° C When
discharged for
Charge Current (A)
 
Approx. Battery Weight
Approx. acid Qty (1.220 Sp.Gr./cell)
Overall Dimensions
Trickel Charge
Current mA
Type
10 Hr.
10 Hr.
Nominal Monobloc
Unit Voltage
Starting
Finishing
Minimum Ah Input during  Intial Charge
Without
Acid (KG)
± 5%
Filled with Acid (KG)
± 5%
Litres
L
mm
± 3
W
mm
±3
H
mm
±3
Min
Max
Final Voltage
per cell (V)
1.75
1.8
(Conforms to BIS 13369)
_______
2.35
2.70
                 
6EL 130
130
123
12
15.6
7.8
585
44.5
71
3.6
500
187
421
130
520
6EL 150
150
142
12
18
9
675
53.5
78
3.3
500
187
421
150
600
6EL 180
180
171
12
22
11
810
55
74
3.0
500
187
421
180
720



Exide EL+ Range of Tubular Monobloc Batteries

 

CAPACITIES WEIGHTS & DIMENSIONS
 
Capacity in Ah at 27° C When
discharged for
Charge Current (A)
 
Approx. Battery Weight
Approx. acid Qty (1.220 Sp.Gr./cell)
Overall Dimensions
 
Trickel Charge
Current mA
Type
10 Hr.
10 Hr.
Nominal Monobloc
Unit Voltage (V)
Starting
Finishing
Minimum Ah Input during  Intial Charge
Without
Acid (KG)
± 5%
Filled with Acid (KG)
± 5%
Litres
L
mm
± 3
W
mm
±3
H
mm
±3
Constant
Potential
Limiting Current (A)
Min
Max
Final Voltage
per cell (V)
1.75
1.80
(Conforms to BIS 13369)
_______
2.35
2.75
                   
6EL40+
40
38
12
5.00
2.50
180
18.10
28.00
1.33
410
176
249
10.00
40
160
6EL50+
50
47
12
6.00
3.00
225
18.30
28.20
1.33
410
176
249
12.50
50
200
6EL66+
66
63
12
8.00
4.00
300
24.40
40.70
2.33
506
220
293
16.50
70
280

6EL80+

80
76
12
9.60
5.00
360
28.60
44.00
2.10
506
220
293
20.00
80
320



Exide EL+ TALL Tubular Range


CAPACITIES WEIGHTS & DIMENSIONS
 
Capacity in Ah at 27° C When
discharged for
Charge Current (A)
 
Approx. Battery Weight
Approx. acid Qty (1.220 Sp.Gr./cell)
Overall Dimensions
 
Trickel Charge
Current mA
Type
10 Hr.
10 Hr.
Nominal Monobloc
Unit Voltage (V)
Starting
Finishing
Minimum Ah Input during  Intial Charge
Without
Acid (KG)
± 5%
Filled with Acid (KG)
± 5%
Litres
L
mm
± 3
W
mm
±3
H
mm
±3
Constant
Potential
Limiting Current (A)
Min
Max
Final Voltage
per cell (V)
1.75
1.80
(Conforms to BIS 13369)
_______
2.35
2.75
                   
6EL100+
100
95
12
12.00
6.00
450
29.80
56.90
3.70
500
187
421
25.00
100
400
6EL130+
130
123
12
16.00
8.00
585
40.60
66.90
3.60
500
187
421
32.50
130
520
6EL150+
150
142
12
18.00
9.00
675
47.60
71.70
3.30
500
187
421
37.50
150
600

6EL180+

180
171
12
22.00
11.00
810
48.80
70.80
3.00
500
187
421
45.00
180
720